Guide · Commercial

How many toilets are required in an office, school or training centre, and how to fit them in

Written by Xiaoqing CaiSenior Architect · Updated November 2026 · 8 min read

How many toilets are required depends on the building's use and how many people are there at once. Under the NSW building code, an office needs one toilet for every 20 men and every 15 women, with a urinal from the 11th man. A school keeps staff and student toilets separate and needs a urinal from the first male student. A maximum occupancy the certifier accepts often keeps the count low.

The number of toilets an office, school or training centre needs comes from tables in the building code, applied to the number of people using the space at once. So working out how many toilets are required starts with that number, and in most existing tenancies the extra fixtures fit: agree a realistic head count with the certifier and place anything new over the existing plumbing.

In NSW the tables are in Part F4 of the National Construction Code (NCC) 2022, in force until NSW adopts NCC 2025 on 1 May 2027.

How many toilets are required in an office?

An office is a Class 5 building. NCC Table F4D4a counts its employees, owners and managers included, and assumes half are men and half women unless the staff are mostly one sex.

WhoToiletsUrinalsWashbasins
Men1 for up to 20, then 1 more per 20None up to 10 men, 1 for 11 to 25, 2 for 26 to 501 per 30
Women1 for up to 15, then 1 more per 15Not applicable1 per 30

"1 more per 20" includes any part of 20, so 21 men need two toilets. An office of 30 needs one toilet, one urinal and one basin for the 15 men, and one toilet and one basin for the 15 women.

How many toilets does a school need?

A school is Class 9b, with its own table, F4D4f. Staff and students can't share toilets; the code's guide says the split protects the teacher and student relationship. Students are counted at 2 m² per person in a general classroom, so a 100 m² classroom counts as 50.

Male students need one toilet for up to 25 and a urinal for up to 50. Female students need one toilet for up to 10 and two for 11 to 25, and each group needs a basin for up to 10. That urinal surprises people: an office needs none until the 11th man, a school one from the first male student. NSW public schools also follow the Department of Education's own facilities standards.

What about a training centre or RTO that isn't a school?

A training facility is often Class 9b too, as ours was. The code has Class 9b tables for schools, theatres, sports venues, churches and public halls, but none written for adult training, so the BCA consultant chooses the closest fit and the certifier accepts it. I'd settle that choice before anyone draws a layout, because it changes the count more than anything else.

A private college we're working with leased a unit in a Sydney industrial strata building, to train on the open lower floor and keep the offices on the mezzanine. It had one accessible unisex bathroom. Our BCA consultant applied the school-related provisions, which asked for separate student and staff facilities and an extra urinal. Our guide to Class 9b requirements covers the rest of that change of use.

How is the number of people worked out?

How many toilets per person depends first on how people are counted. By default the code divides the floor area of each part by a rate from Table D2D18, and corridors, stairs, toilets and the like aren't counted. If the number can be worked out more accurately, that number is used, and the code's guide lists a statement from the owner where public access is limited.

The rates vary a lot: one person per 10 m² for an office and per 2 m² for a classroom, so the same 200 m² floor is 20 people or 100. For computer training rooms, the guide says to use whichever of the two fits.

On our project we agreed a cap of 20 people at any one time with the BCA consultant, students and staff together, one group per session, and wrote it into the plan of management that goes in with the DA. The college will then run at the numbers the toilets were assessed on, and the exits use the same figure.

UseHow numbers are countedWhat usually decides the count
Office (Class 5)10 m² per person, or the actual staff numberA urinal from the 11th man; one unisex toilet for up to 10 staff
School (Class 9b)2 m² per person in a classroom, 10 m² in a staff roomStaff kept apart from students; a urinal from the first male student
Adult training room (Class 9b)The office or classroom rate, or a stated maximum the certifier acceptsWhich provisions the BCA consultant applies, and the cap

Does an accessible unisex toilet count?

Yes, once for each sex, if it's the accessible toilet the code requires. In an example in the code's guide, 10 toilets for men and 10 for women can be 9, 9 and one accessible unisex toilet. An extra accessible toilet doesn't count twice, and an ambulant cubicle isn't a unisex facility.

A required urinal can't go inside a unisex toilet; it needs a space reserved for men. A toilet can take a urinal's place if it's extra to the toilets already required. Where it goes and what it needs is in our guide to accessible toilets. From 1 May 2027, NCC 2025 adds an optional all-gender route: self-contained rooms with a toilet, a basin and walls to the ceiling.

What does the workplace code add?

Searches for how many toilets are required in a workplace usually lead to SafeWork NSW's code of practice, Managing the work environment and facilities. For workplaces in buildings it points to the building code, and its own minimums are close: one toilet per 20 men, one urinal per 25 men, one toilet per 15 women and a basin per 30 of each.

Its unisex test is stricter, though: 10 or fewer workers and no more than two of one gender. It also asks for enough toilets for the workers who need them at the same time, such as at breaks, and that duty carries on as the team grows. For a college it covers the staff, since students aren't workers.

How do you fit extra toilets into an existing tenancy?

We planned ours around five steps.

Cap the number of people

The cap in the plan of management brings the count down before anything is built. Timetabling groups so they don't overlap does the same.

Put new fixtures over or beside the existing services

In our experience most of the cost of a new toilet or urinal is in the pipe run, so it costs least near the existing waste and vent stacks. We proposed a urinal cubicle and a basin on the mezzanine directly above the existing bathroom, so the plumbing connects to the services below and the new mechanical ventilation to that bathroom's exhaust. The unit would then have two basins, one toilet, one urinal and the shower. Where nothing sits above or below, the wall carrying the existing pipes is usually next best.

Use a performance solution for the student and staff split

Where a standard rule can't be met, a performance solution shows the design still meets the code's performance requirement: facilities suited to the use, the number and gender of the people and their particular needs. We proposed one for the student and staff split, prepared by the BCA consultant for the certifier.

Stop the cubicle walls short of the ceiling

A fully enclosed new room can mean extending the sprinklers into it. Only a unisex toilet needs walls to the ceiling; single-sex cubicles need partitions at least 1.8 m high. So we proposed urinal partitions about 2,200 mm high with a 500 mm gap to the ceiling, and asked the certifier early. The certifier advised the sprinklers could stay as they were, and the fire consultant followed that advice, so we didn't commission fire engineering drawings or a report for the cubicle. Sprinkler layouts differ, so agree the height with your certifier first.

Run the strata approval alongside the DA

In a strata building the slab between floors is often common property. Ours was, so the plumbing needs the owners corporation's approval, through a special resolution and a by-law saying who maintains the new pipes and the exhaust connection. Start it once the location is chosen and run it alongside the DA. Our guide to strata approval for common property works has the steps.

What this means for you

In our experience most tenancies can take the toilets a new use needs with one or two extra fixtures, once the head count and the provisions are settled. Before the layout is drawn:

  • Write down the most people on the premises at once, and the session timetable
  • Ask the BCA consultant which provisions apply
  • List the toilets, urinals and basins already there, and find the waste and vent stacks
  • In a strata building, ask the strata manager what is common property
  • Agree partition heights with the certifier
  • Put the maximum occupancy in the plan of management

Our pre-lease check gives you a written answer on the approval route, what the toilets and access need and a rough budget range, at our hourly rate and credited against our design fee if you go ahead on that site. Our guide to opening a training centre in Sydney covers the rest of the approval, and our office and training space design page shows how we take it from there. Bring us in while the layout is still open, and the extra toilets get planned with everything else.

Questions people ask

How many toilets are required for 50 people in an office?

Under NCC Table F4D4a, 50 staff is counted as 25 men and 25 women. The men need two toilets, one urinal and one washbasin, and the women two toilets and one washbasin. A required accessible unisex toilet counts once for each sex, so it can stand in for one toilet and one basin on each side.

Do staff and students need separate toilets?

In a school, yes. The building code lets employees and the public share toilets in most Class 9b buildings, but not in schools or early childhood centres. For a college or RTO it depends on the provisions the BCA consultant applies, and where the space can't hold two sets, a performance solution can be put to the certifier.

Are unisex toilets allowed in a workplace?

Yes, within limits. The building code allows one unisex toilet instead of separate ones where no more than 10 people are employed, and SafeWork NSW's code adds that no more than two should be of one gender. A unisex toilet has a toilet, a basin and sanitary disposal, with walls to the ceiling. Larger workplaces can add unisex toilets on top of the required male and female ones.